产品中心

Forney 福尼 adVantage风管燃烧器

73
  • 样式:Forney 福尼 adVantage风管燃烧器
  • 规格:Forney 福尼 adVantage风管燃烧器
  • 在线订购

 

Forney 福尼 adVantage风管燃烧器Duct Burners

adVantage风管燃烧器在最具挑战性的条件下运行。优质组件和专利技术的结合,使其性能与其他管道燃烧器不同。

应用规范

管道横截面: 3至50英尺(0.91至15 25米)

热量输入: 10至1100百万英热单位/小时(2 .93至322兆瓦)

入口氧气水平:≥10.5%湿,不增加空气

入口H2O:≤20%, 不增加空气

燃烧器的TEG分布: 90%横截面上平均速度的+20%

adVantage Duct Burners perform in the most challenging conditions. Premium components and patented technology join to perform like no other duct burner.

Application Specifications

Duct cross sections: 3 to 50 feet (0.91 to 15.25 meter)
Heat inputs: 10 to 1100 MMBtu/hr  (2.93 to 322 MW)
Inlet oxygen levels: ≥ 10.5% wet without augmenting air
Inlet H2O: ≤ 20% without augmenting air
TEG distribution to the burner: ± 20% of the average velocity over 90% of the cross section

Typical Emissions

For most advanced gas turbine applications firing natural gas – assuming < 12% wet H2O; Firing Temperatures>1200°F (649°C), we offer the following emission guarantees in HHV over turndown – without augmenting air:

Non-Power Augmentation* Power Augmentation**
lb/MMBtu  (mg/MJ) lb/MMBtu (mg/MJ)
NOx 0.08  (34) 0.08 (34)
CO 0.04  (17) 0.06 (26)
VOC 0.004 (2) 0.006 (3 kg/GJ)
PM-10 (front and back half) 0.01 (4) 0.02 (9)